Protect.Computer
NEWS

Six Unpatched Flaws Hit Danfoss AK-SM800A Refrigeration Controllers

· 3 min read · Network safety Device safety
Six Unpatched Flaws Hit Danfoss AK-SM800A Refrigeration Controllers

Dutch security consultancy Midnight Blue says it found six flaws in the Danfoss AK-SM800A, a controller that runs a store’s fridges and freezers, that could let a remote attacker take over the device without logging in. According to The Hacker News, five of the flaws sit in web request handlers that need no login, inside a program that runs as root, and the sixth is in the gateway that enforces the controller’s “Strict mode” login protection. Midnight Blue’s write-up says the affected firmware is every version up to and including 5.3.2, and the Belgian Centre for Cybersecurity (CCB) and Germany’s BSI repeat that range.

There is no patch. The CCB’s advisory says CVE identifiers were still pending and coordinated disclosure with Danfoss was ongoing when it published. The Hacker News reports that Danfoss’s newest release, 5.4.0 from November, mentions no fix and that Midnight Blue says it does not patch the flaws. The BSI first said 5.4.0 was not affected, then corrected its notice on 13 November to say that it cannot rule out that 5.4.0 is affected. The BSI also says it knows of no exploitation of the new flaws, and The Hacker News reports that neither agencies nor researchers link them to the recent attacks on supermarket refrigeration.

The controllers have been in the news since October, when attackers forced defrost cycles at French supermarkets, followed by a second wave across Europe and a joint US advisory. The Hacker News reports that an attacker with code running as root could change the controller’s settings, trigger defrost cycles and hide that activity from the logs, and that because the researchers found no secure boot, planted code could survive a factory reset or firmware update. The researchers call patching flaw by flaw, or relying on Strict mode, “a misallocation of scarce security and personnel resources,” since they expect more flaws in the same code.

How to check if you’re affected

Affected products are Danfoss AK-SM800A controllers running firmware up to and including 5.3.2, and 5.4.0 is not shown to be safe, per the BSI’s corrected notice. Midnight Blue says its recommendations apply to Danfoss, Copeland and Dixell controllers in general.

  • Find every controller whose management interface can be reached from the internet, including through a 4G or 5G modem; the CCB says a modem alone is not a security measure.
  • Remove that exposure and allow remote access only through a secure VPN, a private APN or a protected internal network. The CCB and Midnight Blue (citing CERT-FR) describe filtering by IP address as an intermediate measure rather than a sustainable one.
  • Do not wait for a patch, and do not rely on updating firmware, changing default passwords or enabling Strict mode: the CCB and Ireland’s cyber agency say these are not enough on their own. Danfoss’s own update guide, as quoted by The Hacker News, says the controller should not be directly reachable from the public internet in any version, including with Strict mode on.
  • Review temperature settings, defrost schedules, user accounts and remote-access settings for changes you did not make (CCB). The Hacker News reports that the BSI adds that anyone who suspects a compromise should change all credentials and check that connected equipment works properly.
  • Before cutting off the data the controller sends to your refrigeration service company, check contract and insurance terms and set up protected remote access so monitoring can continue (CCB).

Sources

Related reading