BleepingComputer reports that the US cyber agency CISA is warning about CVE-2026-129713, a critical (CVSS 9.8) stack-based buffer overflow in the server of Danfoss AK-SM 8xxA Series controllers, the units food retailers use to manage refrigeration, HVAC and lighting. According to BleepingComputer, CISA says an attacker can trigger it without logging in, make the server restart and potentially run code with the web server’s privileges. BleepingComputer lists the 820A, 850A and 880A among the models and says CISA does not know how many controllers are deployed.
There is no patch yet. BleepingComputer says Danfoss published a security advisory on November 20 saying the flaw will be fixed in an upcoming 5.5.x software release, which will also remove the option to turn off “Strict mode”. This follows our November 16 report on six unpatched flaws in the AK-SM800A found by Midnight Blue, and the supermarket attacks that France attributed to Iran and the joint US advisory. BleepingComputer’s article does not mention Midnight Blue, but Midnight Blue’s write-up now lists CVE-2026-129713 (CVSS 9.8) for its six stack-based buffer overflows in the AK-SM800A, and says the affected versions are all up to and including 5.4.0 — wider than the “up to 5.3.2” range in our earlier post. Neither source says the flaw has been used in attacks; BleepingComputer recounts the earlier supermarket incidents as background.
How to check if you’re affected
Affected products are Danfoss AK-SM 8xxA Series controllers (AK-SM800A per Midnight Blue), and Midnight Blue lists affected versions as all up to and including 5.4.0. A 5.4.0 controller is therefore not safe, and no fixed version is available yet.
- Find every controller whose web interface can be reached from the internet, including through a cellular modem.
- BleepingComputer lists these actions for administrators: keep controllers off the public internet and minimise network exposure, separate control systems from business networks behind firewalls, and use up-to-date VPNs when remote access is required. Midnight Blue’s mitigation line names VPNs, a private APN or highly restrictive IP allow-lists.
- Watch for Danfoss’s 5.5.x release and read its advisory (DSA-2026-12-01) for the fixed version once it ships. Our check of that page returned an Azure web-firewall challenge, so we did not read it; the planned fix and the Strict-mode change are as BleepingComputer reports them.
Sources
- BleepingComputer: CISA warns of critical unpatched flaw in Danfoss refrigeration controllers
- Midnight Blue: multiple remote code execution vulnerabilities in Danfoss AK-SM800A
- Danfoss security advisory DSA-2026-12-01 (linked from BleepingComputer; returned a web-firewall challenge page, not read directly)
- CISA ICS advisory ICSA-26-328-03 (linked from BleepingComputer; returned “Access Denied”, not read directly)